Laserfiche WebLink
BW <br />C. 7, § 39 BUILDING CODE <br />C. 7, § 39 <br />One story building—seventy-five hundred square feet. <br />Two story building—five thousand square feet. <br />In no case shall the extreme projection of a frame building be <br />erected within five feet of the side or rear lot line, nor within ten <br />feet of another building on the same lot, unless the space between <br />the studs on such side be filled solidly with not less than two and <br />one-half inches of brick work or other equivalent. incombustible <br />material, in which case said distances may be reduced to three feet. <br />Rows of frame tenement houses are prohibited. Duplex or <br />double frame houses shall be permitted. <br />Buildings with wooden framework clad with sheet metal, or <br />veneered with brick, shall be classed as frame buildings. <br />The maximum spacing for studding and joists shall be sixteen <br />inches on centers, that for rafters twenty-four inches. Studding <br />in external ;walls and all partitions of dwellings shall be not less <br />than standard two by fours standing, with studs set the four -inch <br />way for thickness of walls. The exterior of the framework of all <br />dwellings shall be sheathed with sheathing not less than three- <br />fourths inches thick. In case of built-up beams or girders, the <br />splicing of members shall be made over supports. In case of house <br />to be weatherboarded, sheathing may be omitted if framework is <br />sufficiently braced against wind pressure. <br />Where the frame is properly cross -braced, sheathing may be <br />eliminated and wood laths embedded in asphaltic binder directly <br />connected to heavy felt roofing material may be applied directly <br />to the studding when stuccoed according to provisions elsewhere <br />outlined in this chapter. Such lathing material shall meet the ap- <br />proval of the building inspector. Where wire or metal laths are <br />used on sheathing board there must be a furring strip one-half <br />inch thick placed not more than sixteen inches on centers. <br />All floors of wood construction in dwellings shall be constructed <br />of not less than two by eight standard wood joists. All joists and <br />studding around openings such as doors and windows shall be <br />doubled. Openings more than four feet wide in bearing partitions <br />shall be trussed or framed over with beams of ample size to carry <br />the full load above. All headers over four feet in length that butt <br />into trimmers shall be carried on metal joist hangers or mortised <br />and tenoned headers and trimmers. There shall be at least one <br />143 <br />C. 7, § 41 BUILDING CODE C. 7, § 43 <br />Hotels (upper floors), apartment houses, dormitories, <br />hospitals ..................................... 60 lbs. <br />Schools.......................................... 75 lbs. <br />Office buildings (ground floor), corridors, stairs and lob- <br />bies in all buildings of public nature .............. 90 lbs. <br />Assembly rooms, mains floors of theatres, ballrooms, <br />gymnasiums or any rooms to be used for drilling, <br />dancing, grandstands, ordinary stores for light stock 120 lbs. <br />Warehouses and light manufacturing .......... 150 to 300 lbs. <br />Special provision shall be made for heavy concentrated loads. <br />An addition of fifty per cent shall be made for floors carrying <br />moving or travelling machinery. (Id.) <br />Sec. 41. Fire walls in tenement houses. <br />In rows of tenements constructed of brick or other similar ma- <br />terial there shall be a twelve -inch fire wall between each two units. <br />(Id.) <br />Sec. 42. Specifications for sleeping rooms. <br />In all buildings every sleeping room shall be provided with a <br />window opening directly upon a street, yard or court, which <br />windows or openings shall equal in area to at least one-tenth of <br />the floor area of the room. <br />The windows of every sleeping room shall be arranged to open <br />to the extent of one-half their area. <br />In every building every sleeping room shall be, for at least two- <br />thirds of its area, not less than seven feet high from the finished <br />floor to the finished ceiling, and shall be not less than seven feet in <br />width at its narrowest point, and have an area of not less than <br />seventy square feet, except that in hotels the area shall not be less <br />than eighty square feet. ( Code 1932, § 494(32).) <br />Sec.. 43. Chimneys, fireplaces, etc. <br />Except as herein provided all chimneys in every building here- <br />after erected, and all chimneys hereafter altered or rebuilt shall be <br />constructed of brick, stone or concrete. No masonry chimney <br />Ch -lo 145 <br />C. 7, § 40 CHARLOTTEVILI,t CITY CODE C. 7, § 40 <br />horizontal row of two by four pieces in each story to provide a fire <br />stop closing off the entire space between studding. (Code 1932, <br />§ 494(31).) <br />Sec. 40. Joists and floor loads. <br />The following schedule of joist sizes and <br />spacings shall be <br />followed as a minimum for dwellings and tenements, assuming a <br />total load dead and live for sixty pounds to a <br />square foot using <br />seasoned short leaf yellow pine lumber. <br />Maximuni Span for Floor Joist <br />Distance between <br />Size or Equivalent Distance on Centers <br />Bearings <br />2"x8" 12" <br />14'0" <br />16" <br />12' 8" <br />3" x 8" 12" <br />16 0" <br />16" <br />14' 6" <br />2" x 10" 12" <br />17' 6" <br />16" <br />15' 9" <br />3" x 10" 12" <br />19' 3" <br />16" <br />17' 6" <br />2" x 12" 12" <br />20' 0" <br />16" <br />18' 0" <br />3" x 12" 12" <br />23' 0" <br />16" <br />21' 0" <br />2" x 14" 12" <br />23, 8" <br />16" <br />21' 6" <br />2/" x 14" 12" <br />25, 6" <br />16" <br />23' 0" <br />3" x 14" 12" <br />27' 0" <br />16" <br />24' 6" <br />In all buildings hereafter erected, altered, or repaired (where <br />such alterations or repair, in the judgment of the building inspec- <br />tor shall require new floor construction), all floor construction shall <br />be constructed in accordance with the following table of minimum <br />live load requirements: <br />144 <br />C. 7, § 43 CHARLOTTESVILLE CITY CODE C. 7, § 43 <br />shall have walls less than eight inches thick unless it be lined on <br />the inside with well -burned terra cotta or fire clay chimney tile set <br />in Portland cement mortar in which case the wall shall be not less <br />than four inches thick. The lining shall be continuous from the <br />bottom of the flue to its extreme height. In concrete chimney an <br />air space of not less than one inch shall be left between the con- <br />crete and flue lining. <br />No chimney shall be corbeled out more than eight inches from <br />a brick wall, and such corbeling shall consist of at least five courses <br />of brick. <br />All chimneys shall be capped with terra cotta, brick, stone, con- <br />crete or cast iron. <br />The smoke flue of every high pressure steam boiler and every <br />appliance producing a corresponding temperature in a flue, if built <br />of brick, stone, reinforced concrete or other approved masonry, <br />shall have walls not less than twelve inches thick, and the inside <br />four inches of such walls shall be fire brick, laid in fire clay mortar, <br />for a distance of at least twenty-five feet from the point where the <br />smoke connection of the boiler enters the flue. <br />The top of, or any openings in, a chimney shall be at least three <br />feet above the nearest partition of the roof. <br />No chimney in any building shall have wooden supports of any <br />kind. Supports shall be incombustible and shall rest upon the <br />ground or the foundation on approved mortar stumps. <br />All chimneys which are dangerous from any cause shall be re- <br />paired and made safe or taken down. <br />Metal smokestacks may be permitted for boilers, furnaces and <br />similar apparatus where large hot fires are used, provided they <br />may have a clearance from all combustible material of not less than <br />one-half the diameter of the stack, but not less than fifteen inches <br />unless the combustible material be properly guarded by loose -fit- <br />ting metal shields, in which case the distance shall not be less than <br />twelve inches. Where such stack passes through a roof, it shall be <br />guarded by a galvanized iron ventilating thimble extending from <br />at least nine inches below the under side of the ceiling or roof <br />beams to at least nine inches above the roof, and the diameter of <br />the ventilating thimble shall be not less than thirty-six inches <br />greater than that of the smokestack. <br />146 <br />1 <br />1 <br />1 <br />1 <br />1 <br />