Laserfiche WebLink
• (1) The wet vent and its extension to the vent stack is <br />2" in diameter. <br />(2) Each water closet below the top floor is individually <br />back vented. <br />(3) The vent stack is sized as given in Table 5. <br />22.1-113. Table 5—Size of Vent Stacks, Wet Vented Fixtures. <br />Number of Wet -Vented Fixtures Diameter of Vent Stacks <br />Inches <br />1 or 2 bathtubs or showers 2 <br />3 to 5 bathtubs or showers 21/2 <br />6 to 9 bathtubs or showers 3 <br />10 to 16 bathtubs or showers 4 <br />Exception—In multistory bathroom groups, wet vented in <br />accordance with paragraph 3 of the water closets below the <br />top floor need not be individually vented if the 2" waste con- <br />nects directly into the water closet bend. <br />22.1-114. Stack Venting. <br />(c) Vent Connections. <br />• When the circuit, loop, or relief vent connections are taken <br />off the horizontal branch, the vent branch connection shall <br />be taken off at a Vial angle or from the top of the hori- <br />zontal branch. <br />(d) Fixtures Back=to_Ba cit 4n Battery. <br />b9� <br />When fixtures are conn f -ted to one horizontal branch <br />through a double wye or a double sanitary tee in a vertical <br />position, a common vent for each two fixtures back-to-back <br />or double connection shall be provided. The common vent shall <br />be installed in a vertical position as a continuation of the <br />double connection. <br />I <br />22.1-116. Relief Vent. <br />(a) Stacks of More than 10 Branch Intervals. <br />Soil and waste stacks in buildings having more than 10 <br />branch intervals shall be provided with a relief at each tenth <br />interval installed, beginning with the top floor. The size of <br />the relief vent shall be equal to the size of the vent stack to <br />which it connects. The lower end of each relief vent shall <br />• <br />connect to the soil or waste stack through a wye below the <br />horizontal branch serving the floor and the upper end shall <br />connect to the vent stack through a wye not less than 3 feet <br />above the floor level. <br />(b) Offsets at an Angle Less than 45 Degrees from the <br />Horizontal in Buildings of Five or More Stories. <br />Offsets less than 45 degrees from the horizontal, in a soil <br />or waste stack, shall comply with paragraphs on Separate <br />Venting and Offset Reliefs. <br />(c) Separate Venting. <br />Such offsets may be vented as two separate soil or waste <br />stacks, namely, the stack section below the offset and the <br />stack section above the offset. <br />(d) Offset Reliefs. <br />Such offsets may be vented by installing a relief vent as a <br />vertical continuation of the lower section of the stack or as a <br />side vent connected to the lower section between the offset and <br />the next lower fixture or horizontal branch. The upper section <br />of the offset shall be provided with a yoke vent. The diameter <br />of the vents shall not be less than the diameter of the main <br />vent, or of the soil or waste stack, whichever is the smaller. <br />22.1-117. Main Vent to Connect at Base. <br />All main vents or vent stacks shall connect full size at their <br />base to the building drain or to the main soil or waste pipe, <br />at or below the lowest fixture branch. All vent pipes shall <br />extend undiminished in size above the roof, or shall be re- <br />connected with the main soil or waste vent. <br />22.1-118. Vent Headers. <br />Stack vents and vent stacks may be connected into a com- <br />mon vent header at the top of the stacks and then extend to <br />the open air at one point. This header shall be sized in accord- <br />ance with the requirements of Table 6, the number of units <br />being the sum of all units on all stacks connected thereto and <br />the developed length being the longest vent length from the <br />intersection at the base of the most distant stack to the vent <br />terminal in the open air as the direct extension of one stack. <br />22.1-119. Size and Length of Vents. <br />(a) Length of Vent Stacks. <br />The length of the vent stack or main vent shall be its de- <br />veloped length from the lowest connection of the vent system <br />with the soil stack, waste stack, or building drain to the vent <br />stack terminal, if it terminates separately in the open air, or to <br />the connection of the vent stack with the stack vent, plus the <br />developed length of the stack vent from the connection to <br />the terminal in the open air, if the two vents are connected <br />together with a single extension to the open air. <br />(b) Size of Individual Vents. <br />The diameter of an individual vent shall be not less than <br />11/2 inches nor less than one-half the diameter of the drain to <br />which it is connected. <br />(c) Size of Relief Vent. <br />The diameter of a relief vent shall be not less than one-half <br />the diameter of the soil or waste branch to which it is con- <br />nected. <br />(d) Size of Circuit or Loop Vent. <br />The diameter of a circuit or loop vent shall be not less than <br />one-half the size of the diameter of the horizontal soil or <br />waste branch or the diameter of the vent stack, whichever is <br />smaller. <br />(e) Size of Vent Piping. <br />The nominal size of vent piping shall be determined from its <br />length and the total of fixture units connected thereto, as <br />provided in Table 6. Twenty per cent of the maximum length <br />may be installed in a horizontal position. <br />(a) One Bathroom Group. <br />A group of fixtures, consisting of one bathroom group and <br />• <br />a kitchen sink or combination fixture, may be installed with- <br />out individual fixture vent, in a one story building on the <br />top floor of a building, provided each fixture drain connects <br />independently to the stack, and the bathtub or shower stall <br />drain enters the stack at the same level or into the water closet <br />bend. <br />All fixtures discharging downstream from a water closet <br />shall be vented. <br />(b) Limits of Fixture Units Above Bathtubs and Water <br />Closets. <br />A fixture or combination of fixtures whose total discharge <br />rating is not more than 3 fixture units, may discharge into a <br />Cb <br />stack not less than 3 inches in diameter without reventing, <br />provided such fixture connections are made above the con- <br />nection to the highest water closet or bathtub tee-wye, and <br />the fixture -unit rating of the stack is not otherwise exceeded. <br />22.1-115. Circuit and Loop Venting. <br />(a) Battery Venting. <br />A branch soil or waste pipe to which two but not more <br />than eight water closets, pedestal urinals, shower stalls, or <br />floor drains are connected in battery, shall be vented by a <br />circuit or loop vent which shall take off in front of the last <br />fixture connection. In addition, lower floor branches serving <br />more than three water closets shall be provided with a relief <br />vent taken off in front of the first fixture connection. When <br />lavatories or similar fixtures discharge above ,such branches, <br />each vertical branch shall be provided with a continuous vent. <br />(b) Dual Branches. <br />When parallel horizontal branches serve a total of eight <br />water closets (four on each branch), each branch shall be <br />provided with a relief vent at a point between the two most <br />distant water closets. When other fixtures (than water clos- <br />ets) discharge above the horizontal branch, each such fixture <br />shall be vented. <br />(c) Vent Connections. <br />• When the circuit, loop, or relief vent connections are taken <br />off the horizontal branch, the vent branch connection shall <br />be taken off at a Vial angle or from the top of the hori- <br />zontal branch. <br />(d) Fixtures Back=to_Ba cit 4n Battery. <br />b9� <br />When fixtures are conn f -ted to one horizontal branch <br />through a double wye or a double sanitary tee in a vertical <br />position, a common vent for each two fixtures back-to-back <br />or double connection shall be provided. The common vent shall <br />be installed in a vertical position as a continuation of the <br />double connection. <br />I <br />22.1-116. Relief Vent. <br />(a) Stacks of More than 10 Branch Intervals. <br />Soil and waste stacks in buildings having more than 10 <br />branch intervals shall be provided with a relief at each tenth <br />interval installed, beginning with the top floor. The size of <br />the relief vent shall be equal to the size of the vent stack to <br />which it connects. The lower end of each relief vent shall <br />• <br />connect to the soil or waste stack through a wye below the <br />horizontal branch serving the floor and the upper end shall <br />connect to the vent stack through a wye not less than 3 feet <br />above the floor level. <br />(b) Offsets at an Angle Less than 45 Degrees from the <br />Horizontal in Buildings of Five or More Stories. <br />Offsets less than 45 degrees from the horizontal, in a soil <br />or waste stack, shall comply with paragraphs on Separate <br />Venting and Offset Reliefs. <br />(c) Separate Venting. <br />Such offsets may be vented as two separate soil or waste <br />stacks, namely, the stack section below the offset and the <br />stack section above the offset. <br />(d) Offset Reliefs. <br />Such offsets may be vented by installing a relief vent as a <br />vertical continuation of the lower section of the stack or as a <br />side vent connected to the lower section between the offset and <br />the next lower fixture or horizontal branch. The upper section <br />of the offset shall be provided with a yoke vent. The diameter <br />of the vents shall not be less than the diameter of the main <br />vent, or of the soil or waste stack, whichever is the smaller. <br />22.1-117. Main Vent to Connect at Base. <br />All main vents or vent stacks shall connect full size at their <br />base to the building drain or to the main soil or waste pipe, <br />at or below the lowest fixture branch. All vent pipes shall <br />extend undiminished in size above the roof, or shall be re- <br />connected with the main soil or waste vent. <br />22.1-118. Vent Headers. <br />Stack vents and vent stacks may be connected into a com- <br />mon vent header at the top of the stacks and then extend to <br />the open air at one point. This header shall be sized in accord- <br />ance with the requirements of Table 6, the number of units <br />being the sum of all units on all stacks connected thereto and <br />the developed length being the longest vent length from the <br />intersection at the base of the most distant stack to the vent <br />terminal in the open air as the direct extension of one stack. <br />22.1-119. Size and Length of Vents. <br />(a) Length of Vent Stacks. <br />The length of the vent stack or main vent shall be its de- <br />veloped length from the lowest connection of the vent system <br />with the soil stack, waste stack, or building drain to the vent <br />stack terminal, if it terminates separately in the open air, or to <br />the connection of the vent stack with the stack vent, plus the <br />developed length of the stack vent from the connection to <br />the terminal in the open air, if the two vents are connected <br />together with a single extension to the open air. <br />(b) Size of Individual Vents. <br />The diameter of an individual vent shall be not less than <br />11/2 inches nor less than one-half the diameter of the drain to <br />which it is connected. <br />(c) Size of Relief Vent. <br />The diameter of a relief vent shall be not less than one-half <br />the diameter of the soil or waste branch to which it is con- <br />nected. <br />(d) Size of Circuit or Loop Vent. <br />The diameter of a circuit or loop vent shall be not less than <br />one-half the size of the diameter of the horizontal soil or <br />waste branch or the diameter of the vent stack, whichever is <br />smaller. <br />(e) Size of Vent Piping. <br />The nominal size of vent piping shall be determined from its <br />length and the total of fixture units connected thereto, as <br />provided in Table 6. Twenty per cent of the maximum length <br />may be installed in a horizontal position. <br />